Staco 924

0.75 kW - 18 kW
Single Phase, On-Line Double Conversion Emergency Lighting Inverter System (ELIS)

The Staco 924 full range of centralized lighting inverters extend from 0.95kW to 18kW and provide full power protection for all emergency lighting applications.

The Voltage and Frequency Independent (VFI) design provides exceptional voltage regulation and ensures lumens, drivers and ballasts on the Staco 924-protected circuit are fully operable when most needed - for egress lighting.

With the highest level of power protection, a full range of power capacities to fit installation needs, and one of the best warranties in the industry, the Staco 924 is the ideal solution for all emergency lighting requirements.

 


Specifications
The Staco 924 maintains efficient AC Emergency Power to operate all emergency lighting fixtures at “full-light” output, providing superior dependability and security to commercial/industrial environments in a small footprint.

  • True online, double conversion technology; highest level of secure power protection available
  • Full LCD display indicates all operating parameters for easy, immediate monitoring
  • Temperature compensated battery charging maximizes battery life
  • Sealed maintenance free batteries.
  • Full light output for 90 minutes.
  • Pure sine wave output for all types of lamps.
  • Backup solutions for multiple applications including:
    indoor and outdoor emergency lighting, exits, cash registers, computers, strategic electronics
  • Meets federal, state and local codes: UL924, NFPA 101, NFPA 70, NEC and OSHA.
  • Cities of Chicago and New York Approved.
  • Complies with the Buy American Act.

Applications

  • Schools, universities, colleges
  • Hospitals, clinics, nursing homes
  • Bridges, tunnels, tollbooths
  • Stadiums, sports arenas, racetracks
  • Shopping malls, retail stores, movie theatres
  • Railroads, subways, airports, mass transit infrastructure
  • Hotels, casinos, resorts
  • Office, financial and industrial complexes
  • Prisons, federal buildings, military compounds

Power Rating (kW): 0.75 kW
Input Voltage: 120, 208, 240, 277, 480
Output Voltage: 120, 208, 240, 277, 480, 120/208, 120/240, 120/277, 208/240, 208/277, 240/277
Battery Runtime (min): 45, 60, 90, 120, 240
Unit Options: AS400 Relay Card: (Hardwired)
AS400 Relay Card: (Serial)
Dimmer (uses 3 distribution poles)
Environmental Sensor Kit
Maintenance Wrap Around Bypass
NEMA 1 w/ Seismic Kit
NEMA 3R (requires enclosure)
NEMA 4X (requires enclosure)
Normally On
Normally Off and Hold Output Voltage (1) & (2)
SNMP Card
10A 1-Pole
10A 1-Pole w/ Trip Alarm
15A 1-Pole
15A 1-Pole w/ Trip Alarm
15A 2-Pole
15A 2-Pole w/ Trip Alarm
20A 1-Pole
20A 1-Pole w/ Trip Alarm
20A 2-Pole
20A 2-Pole w/ Trip Alarm
30A 1-Pole
30A 1-Pole w/ Trip Alarm
30A 2-Pole
30A 2-Pole w/ Trip Alarm
Power Rating (kW): 0.95 kW
Input Voltage: 120, 208, 240, 277, 480
Output Voltage: 120, 208, 240, 277, 480, 120/208, 120/240, 120/277, 208/240, 208/277, 240/277
Battery Runtime (min): 45, 60, 90, 120, 240
Unit Options: AS400 Relay Card: (Hardwired)
AS400 Relay Card: (Serial)
Dimmer (uses 3 distribution poles)
Environmental Sensor Kit
Maintenance Wrap Around Bypass
NEMA 1 w/ Seismic Kit
NEMA 3R (requires enclosure)
NEMA 4X (requires enclosure)
Normally On
Normally Off and Hold Output Voltage (1) & (2)
SNMP Card
10A 1-Pole
10A 1-Pole w/ Trip Alarm
15A 1-Pole
15A 1-Pole w/ Trip Alarm
15A 2-Pole
15A 2-Pole w/ Trip Alarm
20A 1-Pole
20A 1-Pole w/ Trip Alarm
20A 2-Pole
20A 2-Pole w/ Trip Alarm
30A 1-Pole
30A 1-Pole w/ Trip Alarm
30A 2-Pole
30A 2-Pole w/ Trip Alarm
Power Rating (kW): 1.15 kW
Input Voltage: 120, 208, 240, 277, 480
Output Voltage: 120, 208, 240, 277, 480, 120/208, 120/240, 120/277, 208/240, 208/277, 240/277
Battery Runtime (min): 45, 60, 90, 120, 240
Unit Options: AS400 Relay Card: (Hardwired)
AS400 Relay Card: (Serial)
Dimmer (uses 3 distribution poles)
Environmental Sensor Kit
Maintenance Wrap Around Bypass
NEMA 1 w/ Seismic Kit
NEMA 3R (requires enclosure)
NEMA 4X (requires enclosure)
Normally On
Normally Off and Hold Output Voltage (1) & (2)
SNMP Card
10A 1-Pole
10A 1-Pole w/ Trip Alarm
15A 1-Pole
15A 1-Pole w/ Trip Alarm
15A 2-Pole
15A 2-Pole w/ Trip Alarm
20A 1-Pole
20A 1-Pole w/ Trip Alarm
20A 2-Pole
20A 2-Pole w/ Trip Alarm
30A 1-Pole
30A 1-Pole w/ Trip Alarm
30A 2-Pole
30A 2-Pole w/ Trip Alarm
Power Rating (kW): 1.75 kW
Input Voltage: 120, 208, 240, 277, 480
Output Voltage: 120, 208, 240, 277, 480, 120/208, 120/240, 120/277, 208/240, 208/277, 240/277
Battery Runtime (min): 45, 60, 90, 120, 240
Unit Options: AS400 Relay Card: (Hardwired)
AS400 Relay Card: (Serial)
Dimmer (uses 3 distribution poles)
Environmental Sensor Kit
Maintenance Wrap Around Bypass
NEMA 1 w/ Seismic Kit
NEMA 3R (requires enclosure)
NEMA 4X (requires enclosure)
Normally On
Normally Off and Hold Output Voltage (1) & (2)
SNMP Card
10A 1-Pole
10A 1-Pole w/ Trip Alarm
15A 1-Pole
15A 1-Pole w/ Trip Alarm
15A 2-Pole
15A 2-Pole w/ Trip Alarm
20A 1-Pole
20A 1-Pole w/ Trip Alarm
20A 2-Pole
20A 2-Pole w/ Trip Alarm
30A 1-Pole
30A 1-Pole w/ Trip Alarm
30A 2-Pole
30A 2-Pole w/ Trip Alarm
Power Rating (kW): 2.44 kW
Input Voltage: 120, 208, 240, 277, 480
Output Voltage: 120, 208, 240, 277, 480, 120/208, 120/240, 120/277, 208/240, 208/277, 240/277
Battery Runtime (min): 45, 60, 90, 120, 240
Unit Options: AS400 Relay Card: (Hardwired)
AS400 Relay Card: (Serial)
Dimmer (uses 3 distribution poles)
Environmental Sensor Kit
Maintenance Wrap Around Bypass
NEMA 1 w/ Seismic Kit
NEMA 3R (requires enclosure)
NEMA 4X (requires enclosure)
Normally On
Normally Off and Hold Output Voltage (1) & (2)
SNMP Card
10A 1-Pole
10A 1-Pole w/ Trip Alarm
15A 1-Pole
15A 1-Pole w/ Trip Alarm
15A 2-Pole
15A 2-Pole w/ Trip Alarm
20A 1-Pole
20A 1-Pole w/ Trip Alarm
20A 2-Pole
20A 2-Pole w/ Trip Alarm
30A 1-Pole
30A 1-Pole w/ Trip Alarm
30A 2-Pole
30A 2-Pole w/ Trip Alarm
Power Rating (kW): 3 kW
Input Voltage: 120, 208, 240, 277, 480
Output Voltage: 120, 208, 240, 277, 480, 120/208, 120/240, 120/277, 208/240, 208/277, 240/277
Battery Runtime (min): 45, 60, 90, 120, 240
Unit Options: AS400 Relay Card: (Hardwired)
AS400 Relay Card: (Serial)
Dimmer (uses 3 distribution poles)
Environmental Sensor Kit
Maintenance Wrap Around Bypass
NEMA 1 w/ Seismic Kit
NEMA 3R (requires enclosure)
NEMA 4X (requires enclosure)
Normally On
Normally Off and Hold Output Voltage (1) & (2)
SNMP Card
10A 1-Pole
10A 1-Pole w/ Trip Alarm
15A 1-Pole
15A 1-Pole w/ Trip Alarm
15A 2-Pole
15A 2-Pole w/ Trip Alarm
20A 1-Pole
20A 1-Pole w/ Trip Alarm
20A 2-Pole
20A 2-Pole w/ Trip Alarm
30A 1-Pole
30A 1-Pole w/ Trip Alarm
30A 2-Pole
30A 2-Pole w/ Trip Alarm
Power Rating (kW): 4.2 kW
Input Voltage: 120, 208, 240, 277, 480
Output Voltage: 120, 208, 240, 277, 480, 120/208, 120/240, 120/277, 208/240, 208/277, 240/277
Battery Runtime (min): 45, 60, 90, 120, 240
Unit Options: AS400 Relay Card: (Hardwired)
AS400 Relay Card: (Serial)
Dimmer (uses 3 distribution poles)
Environmental Sensor Kit
Maintenance Wrap Around Bypass
NEMA 1 w/ Seismic Kit
NEMA 3R (requires enclosure)
NEMA 4X (requires enclosure)
Normally On
Normally Off and Hold Output Voltage (1) & (2)
SNMP Card
10A 1-Pole
10A 1-Pole w/ Trip Alarm
15A 1-Pole
15A 1-Pole w/ Trip Alarm
15A 2-Pole
15A 2-Pole w/ Trip Alarm
20A 1-Pole
20A 1-Pole w/ Trip Alarm
20A 2-Pole
20A 2-Pole w/ Trip Alarm
30A 1-Pole
30A 1-Pole w/ Trip Alarm
30A 2-Pole
30A 2-Pole w/ Trip Alarm
Power Rating (kW): 6 kW
Input Voltage: 120, 208, 240, 277, 480
Output Voltage: 120, 208, 240, 277, 480, 120/208, 120/240, 120/277, 208/240, 208/277, 240/277
Battery Runtime (min): 45, 60, 90, 120, 240
Unit Options: AS400 Relay Card: (Hardwired)
AS400 Relay Card: (Serial)
Dimmer (uses 3 distribution poles)
Environmental Sensor Kit
Maintenance Wrap Around Bypass
NEMA 1 w/ Seismic Kit
NEMA 3R (requires enclosure)
NEMA 4X (requires enclosure)
Normally On
Normally Off and Hold Output Voltage (1) & (2)
SNMP Card
10A 1-Pole
10A 1-Pole w/ Trip Alarm
15A 1-Pole
15A 1-Pole w/ Trip Alarm
15A 2-Pole
15A 2-Pole w/ Trip Alarm
20A 1-Pole
20A 1-Pole w/ Trip Alarm
20A 2-Pole
20A 2-Pole w/ Trip Alarm
30A 1-Pole
30A 1-Pole w/ Trip Alarm
30A 2-Pole
30A 2-Pole w/ Trip Alarm
Power Rating (kW): 8 kW
Input Voltage: 120, 208, 240, 277, 480
Output Voltage: 120, 208, 240, 277, 480, 120/208, 120/240, 120/277, 208/240, 208/277, 240/277
Battery Runtime (min): 45, 60, 90, 120, 240
Unit Options: AS400 Relay Card: (Hardwired)
AS400 Relay Card: (Serial)
Dimmer (uses 3 distribution poles)
Environmental Sensor Kit
Maintenance Wrap Around Bypass
NEMA 1 w/ Seismic Kit
NEMA 3R (requires enclosure)
NEMA 4X (requires enclosure)
Normally On
Normally Off and Hold Output Voltage (1) & (2)
SNMP Card
10A 1-Pole
10A 1-Pole w/ Trip Alarm
15A 1-Pole
15A 1-Pole w/ Trip Alarm
15A 2-Pole
15A 2-Pole w/ Trip Alarm
20A 1-Pole
20A 1-Pole w/ Trip Alarm
20A 2-Pole
20A 2-Pole w/ Trip Alarm
30A 1-Pole
30A 1-Pole w/ Trip Alarm
30A 2-Pole
30A 2-Pole w/ Trip Alarm
Power Rating (kW): 10 kW
Input Voltage: 120, 208, 240, 277, 480
Output Voltage: 120, 208, 240, 277, 480, 120/208, 120/240, 120/277, 208/240, 208/277, 240/277
Battery Runtime (min): 45, 60, 90, 120, 240
Unit Options: AS400 Relay Card: (Hardwired)
AS400 Relay Card: (Serial)
Dimmer (uses 3 distribution poles)
Environmental Sensor Kit
Maintenance Wrap Around Bypass
NEMA 1 w/ Seismic Kit
NEMA 3R (requires enclosure)
NEMA 4X (requires enclosure)
Normally On
Normally Off and Hold Output Voltage (1) & (2)
SNMP Card
10A 1-Pole
10A 1-Pole w/ Trip Alarm
15A 1-Pole
15A 1-Pole w/ Trip Alarm
15A 2-Pole
15A 2-Pole w/ Trip Alarm
20A 1-Pole
20A 1-Pole w/ Trip Alarm
20A 2-Pole
20A 2-Pole w/ Trip Alarm
30A 1-Pole
30A 1-Pole w/ Trip Alarm
30A 2-Pole
30A 2-Pole w/ Trip Alarm
Power Rating (kW): 10.8 kW
Input Voltage: 120, 208, 240, 277, 480
Output Voltage: 120, 208, 240, 277, 480, 120/208, 120/240, 120/277, 208/240, 208/277, 240/277
Battery Runtime (min): 45, 60, 90, 120, 240
Unit Options: AS400 Relay Card: (Hardwired)
AS400 Relay Card: (Serial)
Dimmer (uses 3 distribution poles)
Environmental Sensor Kit
Maintenance Wrap Around Bypass
NEMA 1 w/ Seismic Kit
NEMA 3R (requires enclosure)
NEMA 4X (requires enclosure)
Normally On
Normally Off and Hold Output Voltage (1) & (2)
SNMP Card
10A 1-Pole
10A 1-Pole w/ Trip Alarm
15A 1-Pole
15A 1-Pole w/ Trip Alarm
15A 2-Pole
15A 2-Pole w/ Trip Alarm
20A 1-Pole
20A 1-Pole w/ Trip Alarm
20A 2-Pole
20A 2-Pole w/ Trip Alarm
30A 1-Pole
30A 1-Pole w/ Trip Alarm
30A 2-Pole
30A 2-Pole w/ Trip Alarm
Power Rating (kW): 16 kW
Input Voltage: 120, 208, 240, 277, 480
Output Voltage: 120, 208, 240, 277, 480, 120/208, 120/240, 120/277, 208/240, 208/277, 240/277
Battery Runtime (min): 45, 60, 90, 120, 240
Unit Options: AS400 Relay Card: (Hardwired)
AS400 Relay Card: (Serial)
Dimmer (uses 3 distribution poles)
Environmental Sensor Kit
Maintenance Wrap Around Bypass
NEMA 1 w/ Seismic Kit
NEMA 3R (requires enclosure)
NEMA 4X (requires enclosure)
Normally On
Normally Off and Hold Output Voltage (1) & (2)
SNMP Card
10A 1-Pole
10A 1-Pole w/ Trip Alarm
15A 1-Pole
15A 1-Pole w/ Trip Alarm
15A 2-Pole
15A 2-Pole w/ Trip Alarm
20A 1-Pole
20A 1-Pole w/ Trip Alarm
20A 2-Pole
20A 2-Pole w/ Trip Alarm
30A 1-Pole
30A 1-Pole w/ Trip Alarm
30A 2-Pole
30A 2-Pole w/ Trip Alarm
Power Rating (kW): 18 kW
Input Voltage: 120, 208, 240, 277, 480
Output Voltage: 120, 208, 240, 277, 480, 120/208, 120/240, 120/277, 208/240, 208/277, 240/277
Battery Runtime (min): 45, 60, 90, 120, 240
Unit Options: AS400 Relay Card: (Hardwired)
AS400 Relay Card: (Serial)
Dimmer (uses 3 distribution poles)
Environmental Sensor Kit
Maintenance Wrap Around Bypass
NEMA 1 w/ Seismic Kit
NEMA 3R (requires enclosure)
NEMA 4X (requires enclosure)
Normally On
Normally Off and Hold Output Voltage (1) & (2)
SNMP Card
10A 1-Pole
10A 1-Pole w/ Trip Alarm
15A 1-Pole
15A 1-Pole w/ Trip Alarm
15A 2-Pole
15A 2-Pole w/ Trip Alarm
20A 1-Pole
20A 1-Pole w/ Trip Alarm
20A 2-Pole
20A 2-Pole w/ Trip Alarm
30A 1-Pole
30A 1-Pole w/ Trip Alarm
30A 2-Pole
30A 2-Pole w/ Trip Alarm

Choose Your Location

Find a distributor in your area.

map

© 2022 Staco Energy Products Co. All Rights Reserved